The Fire Water Pump is an API 610 Type VS1 vertical, single casing, multistage turbine pump specifically engineered for fire protection water supply from wells, reservoirs, rivers, or wet pits. The pump fully complies with API 610 11th Edition and ISO 13709 standards, with optional compliance to NFPA 20 for fire pump service.
In fire protection systems, the VS1 pump draws water from a static source (dedicated fire water tank, river, pond, or deep well) and delivers it at required pressure to the plant fire water ring main, hydrants, sprinklers, or deluge systems. The vertical turbine configuration is preferred when suction conditions are insufficient for horizontal fire pumps or when the water source is below grade.
The VS1 design features a submerged bowl assembly below minimum water level, line shaft transmitting power from above-grade driver, and multistage impellers providing required pressure. This eliminates priming concerns and cavitation risks associated with suction lift.
As a specialized China API 610 pump manufacturer, we produce VS1 fire water pumps for critical fire protection service in refineries, petrochemical complexes, power plants, and industrial facilities.
| Medium | Suitability |
|---|---|
| Clean fresh water | Excellent – standard construction |
| Raw water / River water | Good – with strainer and moderate solids tolerance |
| Sea water / Brackish water | Good – with duplex stainless steel or bronze |
| Fire water with additives | Good – with compatible materials (AFFF foam concentrate compatible) |
The pump is designed for clean or slightly polluted water as typically encountered in fire water storage.
| Parameter | Range |
|---|---|
| Flow rate (Q) | 50 ~ 5,000 m³/h (typical fire pump ratings) |
| Total head (H) | 50 ~ 200 m (7 ~ 30 bar) |
| Operating temperature | -20°C ~ +80°C |
| Design pressure | Up to 2.5 MPa (25 bar) |
| Speed | 1,450 / 2,980 rpm (50 Hz) or 1,750 / 3,550 rpm (60 Hz) |
| Flange rating | ASME Class 150 / 300 |
| Installation depth | Up to 30 m |
| Feature | Benefit |
|---|---|
| Vertically suspended submerged pump | Impeller always submerged – no priming required, no suction lift issues |
| Multistage diffuser type | Develops required fire water pressure through stacked stages |
| Single or double suction first stage | Single suction standard; double suction for ultra low NPSH applications |
| Line shaft with centralizers | Transmits torque from driver to submerged bowl assembly; centralizers prevent shaft vibration |
| Stainless steel column pipe | Threaded or flanged connections; corrosion resistant for long service life |
| Axial thrust balancing | Balance drum or thrust bearing in discharge head handles hydraulic thrust |
| Renewable wear rings | Maintains efficiency over pump life |
| Packed stuffing box or mechanical seal | Seal at discharge head prevents leakage along shaft; mechanical seal optional for zero emissions |
| Material options | Cast iron, bronze, 304/316SS, duplex for corrosion resistance |
| Driver options | Electric motor (standard), diesel engine (NFPA 20 requirement often), or steam turbine |
| NFPA 20 compliance | Optional: diesel engine drive, overspeed protection, pressure relief, full fire pump controller |
| Component | Fresh Water Service | Sea Water / Corrosive Service |
|---|---|---|
| Bowl casting | Cast iron | 316SS / Duplex |
| Impellers | Bronze (ASTM B148) | 316SS / Duplex / Super Duplex |
| Diffusers | Cast iron / Bronze | 316SS / Duplex |
| Line shaft | AISI 416 stainless steel | 17-4PH / Duplex |
| Column pipe | Carbon steel (FM approved) | 316SS / Duplex |
| Discharge head | Cast iron / Fabricated steel | 316SS |
| Wear rings / Bushings | Bronze / Silicon carbide | Silicon carbide / Stellite |
Compliant with API 610 for heavy duty continuous service
Optional NFPA 20 compliance for fire pump installations
Factory Mutual (FM) or UL listed upon request (subject to certification process)
Diesel engine drive option for reliable power during electrical failure
Complete fire pump package: pump, driver, controller, relief valve, gauges, and piping
| Industry | Fire Water Service |
|---|---|
| Oil refineries | Fire water main supply from storage tanks or wells |
| Petrochemical plants | Process area deluge and hydrant systems |
| LNG / Gas processing | Critical fire protection from deep wells |
| Power plants | Cooling tower fire protection, station service water |
| Storage terminals | Tank farm fire water supply |
| Offshore platforms | Seawater lift for firewater (with duplex materials) |
| Mining | Process plant fire protection |
API 610 11th Edition (ISO 13709) compliance – rigorous design and testing
Optional NFPA 20 compliance – meets fire protection industry standards
Submerged vertical design – eliminates priming and suction lift issues
Multistage high pressure capability – up to 25 bar discharge
Complete material range – cast iron, bronze, 304/316SS, duplex for sea water
Competitive cost – 20–30% lower than Western alternatives
Lead time – 20–28 weeks for standard configurations
Factory testing – full performance test, mechanical run, hydrostatic test
Documentation – performance curves, GA drawings, test reports, material certifications
Complete fire pump packages – pump, driver, controller, auxiliary components
Spare parts – critical components stocked
| Parameter | Specification |
|---|---|
| Pump Type | API 610 Type VS1 – vertical, single casing, diffuser, multistage turbine pump |
| Medium | Fresh water, raw water, sea water (with duplex) |
| Flow range | 50 ~ 5,000 m³/h |
| Head range | 50 ~ 200 m |
| Temperature | -20°C to +80°C |
| Pressure rating | Up to 2.5 MPa (25 bar) |
| Speed | 1,450/2,980 or 1,750/3,550 rpm |
| Casing | Single casing, diffuser type |
| Impellers | Enclosed or semi-open, multistage |
| First stage suction | Single suction (standard); double suction (low NPSH) |
| Installation depth | Up to 30 m |
| Line shaft | 416 stainless steel (standard) |
| Seal | Packed stuffing box; mechanical seal optional |
| Materials | Cast iron, bronze, 304/316SS, duplex |
| Driver | Electric motor (standard); diesel engine (NFPA) |
| Compliance | API 610 11th Edition; optional NFPA 20, FM, UL |
| Certification | API 610 / ISO 13709 |
For more information or a custom proposal for your fire water pump (API 610 VS1) application, please contact us at:
info@hyrig.com
total 0 Sheet,Only 5 images can be uploaded, each less than 5m.