A condensate recovery pump is a specialized vertical turbine pump designed to collect hot condensate – the liquid water formed when steam releases its latent heat – from low‑level collection points such as condensate pits, hot wells, flash tanks, and process drains, and then transfer it to the deaerator, boiler feedwater tank, or return main. Condensate recovery is essential for energy efficiency (reusing high temperature water reduces fuel consumption), water conservation, and chemical treatment savings.
The pump is classified under API 610 (ISO 13709) as Type VS2 – a vertical suspended, wet pit, single-casing diffuser or volute pump. The vertical turbine configuration is ideal for low NPSH service because the pump bowl is submerged below the condensate level, providing positive suction head even when the condensate is near its boiling point. This design eliminates priming concerns, handles intermittent flow, and provides long, trouble‑free operation in steam condensate service.
This pump is manufactured by a leading China API 610 pump manufacturer with full API Q1 certification, decades of experience in high‑temperature pumping, and thousands of VS2 pumps installed in condensate recovery and steam system applications worldwide.
| Feature | Description |
|---|---|
| API 610 Type | VS2 (vertical suspended, wet pit, single‑casing) |
| Casing form | Diffuser type or volute type; single casing |
| Suction | Submerged below condensate level; flooded suction |
| Discharge | Through column to surface discharge head |
| Driver | Surface‑mounted electric motor (dry, accessible) |
| Number of stages | Single‑stage (standard for low head) or multistage (for higher head) |
| Impeller type | Radial or mixed flow, single‑suction or double‑suction first stage |
| Shaft | Flexible line shaft with intermediate sleeve bearings |
| Thrust bearing | Located in driver or discharge head, sized for hydraulic down‑thrust |
| Compliance | API 610 11th / 12th edition (ISO 13709) |
Submerged suction for low NPSH – Condensate is often near its saturation temperature, leaving very low NPSH available. The VS2 pump's submerged bowl design ensures positive NPSH by virtue of the liquid column above the impeller. The vertical turbine type can be specially designed for low NPSH applications.
Vertical orientation – Saves floor space; pump is installed directly in the condensate pit or tank, requiring no separate suction piping.
No priming required – The impeller is always submerged, eliminating the need for foot valves, vacuum priming, or manual filling – critical for intermittent operation where condensate may flash to steam during idle periods.
High temperature capability – Designed for fluids up to 200°C (400°F), with proper materials, thermal expansion allowances, and seal selection.
Flexible setting depth – Column length is customised to the pit depth, allowing the pump to sit just above the pit bottom, maximizing condensate recovery down to low levels.
Easy maintenance – The rotating assembly can be withdrawn upward without draining the pit. The surface‑mounted motor remains dry and accessible.
| Parameter | Range |
|---|---|
| Flow | 10 – 1,000 m³/h (45 – 4,400 GPM) – typical 20‑500 m³/h |
| Head | 15 – 200 m (50 – 655 ft) – typical 30‑100 m |
| Temperature | Up to 200°C (400°F) |
| Maximum pressure | Up to 2.5 MPa (25 bar) |
| Setting depth (column length) | Up to 15 m (custom longer on request) |
| Number of stages | 1 – 6 (depending on head) |
| Speed | 1,450 / 2,900 rpm (50Hz) or 1,750 / 3,550 rpm (60Hz) – slower speeds for low NPSH |
| Flange rating | ANSI Class 150 / 300 |
| NPSHr | Very low (1‑3 m) due to submerged impeller and low‑NPSH first‑stage hydraulics |
| Design life | 20 years minimum |
Condensate is typically deaerated and may be slightly acidic (pH 6‑7) due to dissolved CO₂, but generally not highly corrosive to carbon steel at moderate temperature. However, to prevent rust contamination and extend life, stainless steel internals are recommended.
| Component | Standard Material (Economical) | Upgrade Material (Premium) | Remarks |
|---|---|---|---|
| Discharge head | Carbon steel (ASTM A216 WCB) | 304/316L stainless steel | Carbon steel acceptable for most; stainless for aggressive condensate |
| Pump column / discharge pipe | Carbon steel (epoxy coated) | 304/316L stainless steel | – |
| Bowl assembly (diffuser/volute) | Carbon steel or 304 SS | 316L stainless steel | For temperatures >150°C, 316L preferred |
| Impeller | 304 stainless steel or bronze | 316L stainless steel | 316L resists corrosion and erosion at high temperature |
| Shaft | 410 stainless steel or 4140 (coated) | 316 stainless steel or 17‑4 PH | 17‑4 PH has good high‑temperature strength |
| Wear rings | 304 SS + hard‑facing | 316L SS + Stellite | – |
| Shaft sleeve | 410 SS or 316 SS | 316L SS | – |
| Intermediate bearings (line shaft) | Bronze‑backed rubber (water lubricated) | Silicon carbide / PTFE | – |
| Thrust bearing (in driver) | Heavy‑duty angular contact | Kingsbury tilting pad | For higher thrust loads |
| Fasteners | 304 SS or B7 | 316 SS / Duplex | – |
Typical condensate (pH 6‑8, temperature ≤150°C): Carbon steel column and discharge head, 304/316L stainless steel bowl, impeller, and shaft. This combination provides good corrosion resistance and economy.
Aggressive condensate (low pH, high chlorides from cooling water contamination, temperature >150°C): Full 316L stainless steel wetted parts (column, bowl, impeller, shaft). 316L offers better high‑temperature chloride resistance.
Very high purity condensate (boiler feed quality): 316L stainless steel to avoid any iron oxide contamination entering the boiler.
All materials supplied with EN 10204 Type 3.1 certification and full traceability.
The mechanical seal is located in the discharge head above grade, not submerged. Hot condensate at up to 200°C requires a seal plan that prevents flashing and maintains lubrication.
| Seal Arrangement | API 682 Plan | Suitability for Condensate Recovery |
|---|---|---|
| Single seal with recirculation cooler | Plan 23 | Recommended – external cooler continuously circulates cooled fluid through the seal chamber, preventing flashing and keeping seal faces cool |
| Single seal with external flush | Plan 32 | Acceptable – clean external water (e.g., treated water) injected into seal chamber to cool and clean |
| Single seal with cooled flush from discharge | Plan 21 | Alternate – takes hot water from pump discharge, passes through cooler, then into seal chamber |
| Dual pressurised (Arrangement 3) | Plan 53B | For zero emissions (not typical for condensate) |
| Tandem seal (Arrangement 2) | Plan 52 | For critical applications where any leakage is unacceptable |
Plan 23 is the industry standard for high temperature water/condensate services. A closed loop recirculates fluid from the seal chamber through an external cooler (air or water cooled) and returns cooled fluid to the seal. The seal chamber is always filled with cool, liquid‑phase water, preventing flashing.
Recommended seal faces: Silicon carbide vs. carbon (good for water) or silicon carbide vs. silicon carbide (for higher reliability). Elastomers: Viton (FKM) up to 200°C; Kalrez for extended life.
For very high temperature (>180°C), consider a steam quench (Plan 62) added to Plan 23 to prevent ice formation on the atmosphere side if cold ambient conditions cause condensation.
Condensate at the collection point is often near its saturation temperature (90‑100°C). Without adequate NPSH, cavitation will occur, destroying the pump. The VS2 design is specifically chosen for this challenge.
Submerged impeller – The pump bowl is placed below the minimum condensate level, providing positive NPSH from the liquid column. NPSHa = atmospheric pressure + (height of liquid above impeller) – (vapour pressure). The vapour pressure is near atmospheric, so the liquid column of 1‑3 metres provides enough NPSH margin.
Low NPSH first‑stage hydraulics – Optimised impeller inlet design reduces NPSH required (NPSHr) to ≤ 2 m.
Double suction first‑stage impeller (optional) – Further reduces NPSHr by 30‑40% when NPSHa is extremely limited.
Ensure minimum submergence – The manufacturer specifies a minimum liquid level above the suction bell to prevent vortexing and air ingestion.
Intermittent operation – Condensate pumps often start and stop based on pit level. The pump must be capable of frequent starts, with a motor rated for such duty. The VS2 design with surface motor and flexible shaft is suitable for intermittent service.
Thermal expansion – The column must allow for thermal expansion when handling hot condensate. The discharge head is designed to accommodate shaft and column growth.
Flash steam handling – The pit may contain flash steam. The pump and motor should be protected from prolonged steam exposure (shrouded motor, drainage, etc.).
Low flow protection – During periods of very low condensate flow, the pump may run below minimum continuous stable flow. Provide a recirculation line (bypass to pit) to maintain minimum flow and prevent overheating.
| Industry / Setting | Specific Service |
|---|---|
| Power plants (conventional / combined cycle) | Condensate extraction from condenser hotwell; low pressure heater drain return |
| Refineries & petrochemical plants | Steam trap condensate collection from process heating systems; condensate return from tracing |
| Industrial steam systems (paper, food, chemical) | Condensate pumping from flash tanks, receiver tanks, and collection pits |
| District heating | Condensate return from heat exchangers to central plant |
| Cogeneration (CHP) plants | Steam turbine condensate recovery |
| Marine / ship | Boiler condensate return from steam systems |
API 610 full compliance (VS2) – 11th/12th edition ISO 13709, 20‑year design life, 3‑year continuous operation.
Vertical submerged design – Eliminates priming and low NPSH problems for hot condensate; no foot valve required.
Surface‑mounted driver – Motor remains dry, accessible for service, and protected from pit moisture.
Thermal expansion compensation – Column and shaft designed for high temperature up to 200°C.
Low NPSH capability – Submerged impeller and low‑NPSH hydraulics ensure cavitation‑free operation even with near‑saturation condensate.
High temperature materials – 316L stainless steel option for wetted parts resists high‑temperature corrosion.
API 682 Plan 23 ready – External cooler seal flushing protects seal faces in hot service.
Easy maintenance – Withdrawable rotor; no need to drain pit for seal or bearing inspection.
Proven in condensate service – Thousands of VS2 pumps operating in condensate recovery systems worldwide.
Hydrostatic test – Discharge head, column, and bowl tested at 1.5× design pressure.
Performance test – Water at rated speed per API 610 Grade 2 (Grade 1 optional).
Mechanical run test – 4 hours minimum continuous operation; vibration and bearing temperature recorded.
NPSH test – Optional, when specified (recommended for low NPSH condensate pits).
Impeller dynamic balancing – Grade G6.3 or better.
Material certification – EN 10204 3.1 for all pressure‑containing and wetted parts.
Hot test – For high‑temperature service, thermal cycle test available on request.
Third‑party inspection – Available (DNV, Lloyds, BV, SGS).
| Component | Recommended Quantity |
|---|---|
| Mechanical seal cartridge (API 682 Plan 23 ready) | 1 set |
| Thrust bearing set (driver or discharge head) | 1 set |
| Intermediate line shaft bearing set (per column section) | 1 set per 2‑3 metres |
| Wear ring set (impeller + bowl) | 1 set |
| Impeller (for critical duty) | 1 set |
| Shaft (for critical duty) | 1 |
| Gasket / O‑ring kit (full set) | 1 set |
For detailed selection of the correct API 610 VS2 condensate recovery pump for your steam system or condensate return project – including flow, head, condensate temperature, pit depth (setting depth), NPSHa, material (carbon steel vs. stainless steel), and seal plan – please contact our engineering team.
Email: info@hyrig.com
Our API 610 VS2 condensate recovery pumps are specifically engineered for high‑temperature, low‑NPSH condensate return service – handling up to 200°C with submerged vertical turbine design, eliminating priming and cavitation. Manufactured by a leading China API 610 pump manufacturer, API Q1 certified, with material options for carbon steel or stainless steel, and API 682 Plan 23 seal cooling for long, reliable service.
total 0 Sheet,Only 5 images can be uploaded, each less than 5m.