API 610 BB1 (horizontal axially split, double-suction) and VS4 (vertical long shaft, suspended) pumps for fire water service. NFPA 20 design, high flow, fast priming. Suitable for refineries, terminals, power plants, and industrial fire protection systems. China fire water pump manufacturer.

Conatct For Details
DetailReview(0)Additional

A fire water pump is the heart of any industrial fire protection system. It must deliver high flow at moderate pressure, start instantly upon demand, and run reliably for extended periods. Our API 610 BB1 and VS4 pumps are specifically engineered for fire water duty in refineries, petrochemical plants, LNG terminals, power stations, and large industrial facilities. Both designs fully comply with API 610 11th/12th edition (ISO 13709) and are built to meet NFPA 20 requirements for fire pumps.


API 610 BB1 – Horizontal Split Case Fire Water Pump

Structure match check: API 610 BB1 is defined as a horizontal, axially split, single‑stage, between‑bearings pump with double‑suction impeller. This is the classic horizontal fire pump configuration used where suction supply is from a pressurized main or elevated tank, and space allows horizontal installation.

Why BB1 for fire water?

  • High flow capacity – from 200 to 10,000 m³/h, meeting fire water demand for large facilities.

  • Double‑suction impeller – hydraulically balanced thrust, smooth operation, extended bearing life.

  • Axially split casing – easy inspection of impeller, wear rings, and internal passages without disturbing piping.

  • High efficiency – typically 85-90%, reducing driver size.

  • Rapid priming – horizontal design with flooded suction ensures immediate water delivery.

  • NFPA 20 compliance – available with UL/FM certifications.

  • Head range – up to 150 m, typical fire pump heads 80-120 m.

Typical BB1 fire water applications

  • Refinery main fire water ring main pumps.

  • LNG terminal fire water supply.

  • Power plant fire protection.

  • Industrial park fire main pumps.


API 610 VS4 – Vertical Long Shaft Fire Water Pump

Structure match check: API 610 VS4 is defined as a vertical, single‑casing, rigid shaft, suspended pump with discharge head above the pit cover. This is the classic vertical fire pump configuration used when suction is from a ground‑level storage tank, pond, or reservoir, or when floor space is limited.

Why VS4 for fire water?

  • Space saving – small footprint; pump is installed above a sump or tank, motor at grade.

  • Flooded suction – impeller submerged, ensures instant priming even with suction lift.

  • No priming required – eliminates priming devices, reducing failure points.

  • Suction from tanks or ponds – ideal for water storage tanks at grade or below grade.

  • Easy pump removal – entire assembly can be withdrawn vertically for maintenance without draining the tank.

  • NFPA 20 compliance – vertical fire pump configuration widely accepted.

  • Flow range – 100 to 5,000 m³/h, head up to 150 m.

  • Column pipe length – customizable from 2 to 15+ meters depending on water level.

Typical VS4 fire water applications

  • Fire pumps drawing from underground storage tanks.

  • Suction from ponds, lakes, or rivers for fire protection.

  • Facilities with limited floor space (vertical installation fits in a small pit).

  • Remote fire water stations (skid‑mounted vertical pump).


Comparison & Selection Guide

FeatureBB1 (Horizontal Split Case)VS4 (Vertical Long Shaft)
API 610 typeBB1 – between‑bearings, axially split, double‑suctionVS4 – vertical single‑casing, rigid shaft, suspended
OrientationHorizontalVertical
FootprintLarge (baseplate + motor length)Small (pump pit + motor above)
Suction sourcePressurized main or elevated tankGround tank, pond, reservoir (may have lift)
PrimingRequires flooded suction (no lift)Self‑priming (impeller submerged)
MaintenanceRemove casing top half without pipingWithdraw entire pump vertically
Flow range200 – 10,000 m³/h100 – 5,000 m³/h
Head rangeUp to 150 mUp to 150 m
Best forLarge footprint, pressurized suctionSpace limited, suction from tanks/ponds

Key design features for fire water service (both types)

  • NFPA 20 compliance – All components (pump, driver, controller, fittings) meet NFPA 20 latest edition. Optional UL/FM certification.

  • High reliability materials – Casing: cast iron or ductile iron (standard), carbon steel or stainless steel for corrosive water. Impeller: bronze (ASTM B148 C95800) or stainless steel. Shaft: 17-4PH or 316SS. Wear rings: bronze or stainless.

  • Sealing – For fire water, gland packing is common (low cost, tolerant of intermittent service). Mechanical seals optional (API 682 Plan 11).

  • Bearing housing – Heavy duty, oil lubricated. For continuous readiness, pure oil mist optional.

  • Driver – Electric motor or diesel engine. NFPA requires either. For electric: high starting torque, fast acceleration. For diesel: weekly automatic test start.

  • Testing – Full performance test witnessed per NFPA 20 and API 610. Hydrostatic test of casing.

  • Corrosion protection – Internal epoxy coating for casings; stainless steel fastener hardware. For seawater fire water, specify bronze or duplex wetted parts.

  • Rapid start – Pump must reach rated speed within 10-15 seconds. Overhung designs (VS4) and double‑suction (BB1) achieve this easily.

Why choose our API 610 fire water pumps?

  • Full API 610 compliance – Type BB1 or VS4 verified.

  • NFPA 20 certified – Ready for fire protection system approval.

  • High flow, reliable start – Designed for immediate water delivery upon demand.

  • Corrosion resistant options – Bronze impellers, epoxy coating, stainless steel trim.

  • Short lead time – Standard fire pump configurations available 12-16 weeks (including driver).

  • Global spare parts support – Impellers, shafts, wear rings, bearings, column assemblies (VS4) shipped worldwide.

Quality assurance

  • ISO 9001:2015 certified.

  • NFPA 20 witnessed performance test (flow, head, power, vibration).

  • Hydrostatic test of casing at 1.5× working pressure.

  • Material traceability EN 10204 3.1 / 3.2.

  • NDE – MT, PT, UT as required.

How to specify your fire water pump

Please provide: flow (m³/h), head (m), suction source (pressurized main, tank, pond), water type (clean, brackish, seawater), NPSHa available (m), installation space (horizontal or vertical preferred), driver type (electric or diesel), and required certifications (NFPA 20 only, or UL/FM). We will recommend BB1 or VS4 type, material class (cast iron/bronze/stainless), seal/packing type, and driver details.