API 610 OH1/OH2 fire water pump – horizontal, overhung, single‑stage centrifugal pump engineered for reliable fire protection service in refineries, petrochemical plants, power stations, oil & gas facilities, and large industrial sites. Available in OH1 foot‑mounted (standard) and OH2 centreline‑mounted (for hot water or thermal expansion) configurations. Cast iron or 316L stainless steel wetted parts. Flows to 1,000 m³/h, heads to 150 m. Back pull‑out design, API 682 mechanical seals. Optional UL/FM/NFPA compliance. Manufactured by a certified China API 610 pump manufacturer with API Q1 certification. 20‑year design life, 3‑year continuous operation.

Conatct For Details
DetailReview(0)Additional

Product Overview

A fire water pump is a critical safety component in any industrial facility, providing pressurised water to fire protection systems including sprinklers, hydrants, monitors, deluge systems, and foam proportioning equipment. Unlike general service pumps, fire pumps must start immediately on demand, operate at full capacity under any conditions, and deliver reliable, uninterrupted flow for the duration of a fire event. These pumps are designed for intermittent duty (emergency operation) but must be ready at all times, often tested weekly or monthly according to NFPA 25.

The pump is classified under API 610 (ISO 13709) as Type OH1 (foot‑mounted) or OH2 (centreline‑mounted). The OH1 configuration is suitable for most fire water services with ambient or warm water temperatures up to 80°C. The OH2 centreline‑mounted configuration is recommended for higher temperature water (e.g., from solar‑heated storage tanks) or where thermal expansion could cause misalignment beyond NFPA/API limits. Both are overhung, radially split, single‑stage, end‑suction centrifugal pumps with back pull‑out design.

This pump is manufactured by a leading China API 610 pump manufacturer with full API Q1 certification and can be supplied with optional certification to NFPA 20 (Standard for the Installation of Stationary Pumps for Fire Protection), UL 448 (Pumps for Fire Protection), and FM Approvals standards.

OH1 vs. OH2 Configuration for Fire Water Service

FeatureOH1 (Foot‑mounted)OH2 (Centreline‑mounted)
MountingFeet on casing bottom bolted to baseplateFeet on casing centreline bolted to baseplate
Thermal expansionCasing expands downward; slight shaft riseCasing expands uniformly; shaft alignment maintained
Temperature rangeUp to 80°C (176°F) – typical fire waterUp to 120°C (248°F) – for hot water storage or high ambient
Best forMost industrial fire water systems (ambient water)Facilities with hot water fire protection loops (e.g., solar‑heated tanks, process integration)
API 610 TypeOH1OH2

Which one to choose?

  • Standard fire water (ambient temperature, ‑10 to 40°C) → OH1 foot‑mounted pump. Economical and widely accepted.

  • Hot fire water (>80°C) from heated storage or process → OH2 centreline‑mounted pump to prevent thermal misalignment and ensure reliable start under all conditions.

Construction & API 610 Classification

FeatureDescription
API 610 TypeOH1 (foot‑mounted) or OH2 (centreline‑mounted)
Casing formRadially split, single volute (double volute for larger sizes)
Bearing supportOverhung – impeller overhangs from bearing housing; bearings at drive end
Number of stagesSingle stage
Suction typeEnd suction, single‑suction
Discharge orientationTop or side discharge (vertical or horizontal)
Flange ratingANSI Class 150 / 300 (fire water pressures typically 8‑12 bar)
ComplianceAPI 610 11th / 12th edition (ISO 13709) + optional NFPA 20 / UL 448

Back pull‑out design – The rotating assembly can be removed for inspection, seal replacement, or impeller cleaning without disturbing suction or discharge piping – important for fire pumps that may sit idle for months but must be serviceable quickly.

Heavy‑duty bearing housing – Finned for oil lubrication. L10 bearing life ≥25,000 hours per API 610 (far exceeding NFPA requirements). For diesel driver applications, the pump must withstand the torque and vibration of a diesel engine.

Impeller – Closed (enclosed) radial type for high efficiency over a wide flow range. Fire pumps often run at flows from 50% to 150% of rated capacity (NFPA requirements). The impeller curve should be stable, continuously rising to shut‑off, non‑overloading over the entire operating range.

Materials – Fire pumps are typically constructed with cast iron casings and bronze or stainless steel impellers to resist corrosion from stagnant water and various water qualities. Option for all‑316L stainless steel for aggressive water or seawater.

Fire Pump Specific Requirements (NFPA 20 / UL 448 / FM)

Although this pump is designed and manufactured to API 610, it can also be built to meet the specific requirements of fire protection standards:

  • Certified performance – Fire pump rated capacity and pressure must be verified by an approved testing laboratory such as UL or FM. The pump must produce at least 150% of rated flow at not less than 65% of rated head.

  • Casing pressure rating – Must withstand hydrostatic test pressure of at least 2× rated shut‑off head or 3.5 MPa (500 psi), whichever is greater.

  • Materials – Cast iron casing, bronze fitted (impeller, wear rings, shaft sleeve) or stainless steel construction. No aluminium in pressure‑containing parts.

  • Gaskets – Non‑asbestos, suitable for water.

  • Flanges – Drilled to ANSI B16.1 for cast iron (or B16.5 for steel).

  • Nameplate – Must show rated flow, rated head, rated speed, and certified performance curve.

  • Testing – The pump shall be factory tested per NFPA 20 before shipment, with witness by an approved third party if required.

Our API 610 OH1/OH2 fire pump can be supplied with all necessary certifications and documentation to meet local fire codes and insurance requirements.

Key Technical Specifications (Fire Water Service)

ParameterOH1 (Foot‑mounted)OH2 (Centreline‑mounted)
Flow (rated)10 – 1,000 m³/h (45 – 4,400 GPM)same
Head (rated)20 – 150 m (65 – 490 ft) – typical 40‑120 msame
Shut‑off head110‑120% of rated headsame
Temperature (max)Up to 80°CUp to 120°C
Pressure ratingUp to 2.5 MPa (25 bar)Up to 3.0 MPa (30 bar)
Speed1,450 / 2,900 rpm (50Hz) or 1,750 / 3,500 rpm (60Hz)same
Impeller typeClosed, dynamically balancedsame
Efficiency75‑85% at BEPsame
Casing testHydrostatic at 2× rated pressure or 3.5 MPa minimum per NFPAsame
Design life20 years minimum20 years minimum

Materials – Cast Iron / Bronze or 316L Stainless Steel

ComponentStandard Material (economical)Upgrade Material (corrosive service)
CasingCast iron (ASTM A48 Class 30) epoxy coated316L stainless steel (CF3M)
ImpellerBronze (ASTM B62) or stainless steel316L stainless steel
Shaft2Cr13 stainless steel or 4140 (coated)316 stainless steel
Wear ringsBronze or cast iron316L + Stellite
Shaft sleeve (at seal)Bronze or 2Cr13316 stainless steel
Gaskets / O‑ringsNon‑asbestos / EPDMPTFE / Viton

Material selection notes

  • Standard fresh water – Cast iron casing with bronze impeller is proven for decades of fire pump service. Bronze resists corrosion and maintains clearance even with intermittent use.

  • Brackish or treated water – Upgrade to all‑316L stainless steel if chlorides exceed 500 ppm.

  • Seawater fire protection – Use 316L stainless steel or duplex. Cast iron will corrode rapidly.

Mechanical Seals – API 682 Plan 11 (Standard)

Fire water pumps typically use a single mechanical seal with Plan 11 (self‑flush from pump casing). The seal must be suitable for long idle periods and then immediate start under full load.

Seal ArrangementAPI 682 PlanSuitability
Single cartridge sealPlan 11 (self‑flush)Standard – simple, reliable for clean fire water
Single seal with quenchPlan 62 (water or steam)For areas where salt crystals or ice could form on atmosphere side
Double seal (Arrangement 2)Plan 52For critical plants where zero leakage is required (rare for fire water)

Recommended seal faces – Carbon vs. ceramic (economical) or silicon carbide vs. carbon for longer life. Seal elastomers: EPDM (standard for water) or Viton (for higher temperature).

Note: Some fire codes require packing or a mechanical seal with a visual leak indicator. Our pump can be supplied with gland packing instead of a mechanical seal if specified.

Drivers – Electric Motor or Diesel Engine

Fire pumps can be driven by:

  • Electric motor – NEMA or IEC, TEFC enclosure, with reduced voltage starter (soft start) or across‑the‑line start. Must meet NFPA 20 requirements for availability and service factor.

  • Diesel engine – For backup when electric supply is not reliable. Adapter and flexible coupling designed for diesel engine torsional vibration. The pump must be suitable for engine drive (typically at 1,500 rpm or 1,800 rpm).

Our API 610 OH1/OH2 pump can be supplied with either driver, including baseplate, coupling, and safety guards.

Fire Pump System Components

In a typical fire water pumping system, the pump is installed with:

  • Suction piping – Must be flooded (no suction lift) and of sufficient diameter to avoid cavitation.

  • Discharge check valve – To prevent backflow when the pump stops.

  • Discharge gate (isolation) valve – For maintenance.

  • Pressure relief valve – To prevent overpressure if discharge is blocked.

  • Fire pump controller – Electric or diesel controller, with alarm and start functions.

  • Flow meter – For testing (optional).

  • Jockey pump – A small pump to maintain system pressure and prevent the main fire pump from short‑cycling.

Our pump can be integrated into a complete fire water skid with controller, valves, and piping.

Key Advantages of API 610 OH1/OH2 Fire Water Pump

  • High reliability – API 610 design life 20 years, 3‑year continuous operation – far exceeds typical fire pump requirements (NFPA only requires pump to be serviceable for 20–30 years, not necessarily continuous).

  • Back pull‑out – Quick access for seal inspection or replacement without removing piping.

  • Material flexibility – Cast iron / bronze or 316L SS to match water quality.

  • Compliance options – Can be supplied with UL/FM/NFPA certification, or as a standard API 610 pump for non‑code plants.

  • Wide hydraulic range – Flows to 1,000 m³/h (4,400 GPM), heads to 150 m (490 ft) – covering most fire water duties.

  • Proven in fire service – Thousands of OH1/OH2 pumps in industrial fire protection worldwide.

  • Ease of maintenance – Replaceable wear rings, cartridge seal, and straightforward bearing lubrication.

Quality Assurance & Testing

  • Hydrostatic test – Casing tested at 1.5× design pressure (or 2× rated pressure per NFPA).

  • Performance test – Water at rated speed per API 610 Grade 2. For UL/FM pumps, witness test per NFPA 20.

  • Mechanical run test – 4 hours minimum (API) or 1 hour (NFPA) – both met.

  • Impeller dynamic balancing – Grade G6.3.

  • Material certification – EN 10204 3.1 for all wetted parts.

  • Third‑party inspection – Available (UL, FM, Lloyds, DNV) per customer requirement.

Recommended Spare Parts (Per Pump)

ComponentRecommended Quantity
Mechanical seal kit (Plan 11)1 set
Bearing set (radial + thrust)1 set
Wear ring set (casing + impeller)1 set
Impeller1
Gasket / O‑ring kit1 set

Get a Quote or Engineering Support

For detailed selection of the correct API 610 OH1/OH2 fire water pump for your industrial fire protection system – including flow, head, water temperature, water quality, driver type (electric or diesel), required certifications (API 610 only or UL/FM/NFPA), and baseplate or skid integration – please contact our engineering team.

Email: info@hyrig.com

*Our API 610 OH1/OH2 fire water pumps are specifically engineered for the demanding requirements of industrial fire protection – reliable start‑up, steady performance over a wide flow range, and long service life between inspections. Manufactured by a leading China API 610 pump manufacturer, API Q1 certified, with options for UL/FM/NFPA compliance, cast iron/bronze or stainless steel materials, and electric or diesel drive.*